8
The WAGO-I/O-SYSTEM 750
Technical Data
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Mechanical strength
Vibration resistance acc. to IEC 60068-2-6
Comment to the vibration restistance:
a) Type of oscillation:
sweep with a rate of change of 1 octave per minute
10 Hz f < 57 Hz, const. Amplitude 0,075 mm
57 Hz f < 150 Hz, const. Acceleration 1 g
b) Period of oscillation:
10 sweep per axis in each of the 3 vertical axes
Shock resistance acc. to IEC 60068-2-27
Comment to the shock restistance:
a) Type of impulse: half sinusoidal
b) Intensity of impulse:
15 g peak value, 11 ms maintenance time
c) Route of impulse:
3 impulses in each pos. And neg. direction of the
3 vertical axes of the test object, this means
18 impulses in all
Free fall acc. to IEC 60068-2-32
1m (module in original packing)
Safe electrical isolation
Air and creepage distance acc. to IEC 60664-1
Degree of protection
Degree of protection IP 20
Electromagnetic compatibility*
Directive Test values Strength
class
Evaluation
criteria
Immunity to interference acc. to EN 50082-2 (96)
EN 61000-4-2 4kV/8kV (2/4) B
EN 61000-4-3 10V/m 80% AM (3) A
EN 61000-4-4 2kV (3/4) B
EN 61000-4-6 10V/m 80% AM (3) A
Emission of interference acc. to
EN 50081-2 (94)
Measuring
distance
Class
EN 55011 30 dBµV/m (30m) A
37 dBµV/m
Emission of interference acc. to
EN 50081-1 (93)
Measuring
distance
Class
EN 55022 30 dBµV/m (10m) B
37 dBµV/m
* Exception: 750-630, 750-631