Vue de la page 16
INTEBUS S / Enclosure and specifications
 :$*2Ç,2Ç6<67(0
9
TECHNICAL DATA:
750-304
dig.+analog
750-324
digital
Number of function modules 64 32
Digital peripheral signals 256 64
Analog peripheral signals 32 ---
Configuration possibility via PC or control ---
Bus connection 2 D-SUB with protection against vibration
Voltage supply 24V DC (-15%/+20%)
Input current 105 mA typ; 900 mA max. 85 mA typ.; 500 mA max.
Internal current 400 mA 400 mA
Power jumper contacts blade / spring contact
slide contact, self-cleaning
Maximum current supplied to K-Bus
for internal module use
1.75 A on request
Voltage power jumper contacts 24 V DC
Current power jumper contacts 10A DC
Data contacts slide contacts, 1.5 u hard gold-plated
self-cleaning
Voltage drop via data contacts <1V with 64 wired special function modules
Housing material Polycarbonat, Polyamid 6.6
Marking standard markers WAGO BR247/248
marker cards 8 x 47mm
Wire connection CAGE CLAMP; 0.08mm
2
-2.5mm
2
/AWG 28 -14
Mounting position any position
Type of protection IP 20
Isolation 500 V system / power supply
Operating temperature 0°C...+55°C
Dimensions (mm) W x H x L 51 x 65* x 100 (*from upper edge of the carrier rail)